Model |
SUN-6K-SG01HP3
-EU-AM2
|
SUN-8K-SG01HP3
-EU-AM2
|
SUN-10K-SG01HP3
-EU-AM2
|
SUN-12K-SG01HP3
-EU-AM2
|
SUN-15K-SG01HP3
-EU-AM2
|
SUN-20K-SG01HP3
-EU-AM2
|
||||||
Battery Input Data |
||||||||||||
Battery Type |
Li-lon |
|||||||||||
Battery Voltage Range (V) |
160-700 |
|||||||||||
Max. Charging Current (A) |
37 |
|||||||||||
Max. Discharging Current (A) |
37 |
|||||||||||
Number of battery input |
1 |
|||||||||||
Charging Strategy for Li-Ion Battery |
Self-adaption to BMS |
|||||||||||
PV String Input Data |
||||||||||||
Max. DC Input Power (W) |
7800 |
10400 |
13000 |
15600 |
19500 |
26000 |
||||||
Max. DC Input Voltage (V) |
1000 |
|||||||||||
Start-up Voltage (V) |
800 |
|||||||||||
MPPT Range (V) |
150-850 |
|||||||||||
Full Load DC Voltage Range (V) |
195-850 |
260-850 |
325-850 |
340-850 |
423-850 |
500-850 |
||||||
Rated DC Input Voltage (V) |
600 |
|||||||||||
PV Input Current (A) |
20+20 |
26+20 |
26+26 |
|||||||||
Max. PV I (A) |
23+23 |
32+23 |
32+32 |
|||||||||
No.of MPP Trackers |
2 |
|||||||||||
No.of Strings per MPP Tracker |
1 |
2+1 |
2 |
|||||||||
AC Output Data |
||||||||||||
Rated AC Output and UPS Power (W) |
6000 |
8000 |
10000 |
12000 |
15000 |
20000 |
||||||
Max. AC Output Power (W) |
6600 |
8800 |
11000 |
13200 |
16500 |
22000 |
||||||
AC Output Rated Current (A) |
9.1/8.1 |
12.2/11.6 |
15.2/14.5 |
18.2/17.4 |
22.8/21.8 |
30.3/29 |
||||||
Max. AC Current (A) |
13 |
18 |
22 |
25 |
30 |
35 |
||||||
Max. Continuous AC Passthrough (A) |
80 |
|||||||||||
Peak Power (offff grid) |
1.5 time of rated power, 10 S |
|||||||||||
Generator input/Smart load /AC couple current (A) |
9.1/80/9.1 |
12.2/80/12.2 |
15.2/80/15.2 |
18.2/80/18.2 |
22.8/80/22.8 |
30.3/80/30.3 |
||||||
Power Factor |
0.8 leading to 0.8 lagging |
|||||||||||
Output Frequency and Voltage |
50/60Hz; 3L/N/PE 220/380, 230/400Vac |
|||||||||||
Grid Type |
Three Phase |
|||||||||||
DC injection current (mA) |
<0.5%1n |
|||||||||||
Efficiency |
||||||||||||
Max. Efficiency |
97.6% |
|||||||||||
Euro Efficiency |
97% |
|||||||||||
MPPT Efficiency |
98.9% |
|||||||||||
Protection |
||||||||||||
Integrated |
PV Input Lightning Protection, Anti-islanding Protection, PV String Input Reverse Polarity Protection, Insulation Resistor Detection, Residual Current Monitoring Unit, Output Over Current Protection, Output Shorted Protection, Surge protection |
|||||||||||
Output Over Voltage Protection |
DC Type II/AC Type III |
|||||||||||
Certififications and Standards |
||||||||||||
Grid Regulation |
EN50549, AS4777.2:2015, VDE0126-1-1, IEC61727, VDEN4105-2018, G99 |
|||||||||||
Safety EMC / Standard |
IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 |
|||||||||||
General Data |
||||||||||||
Operating Temperature Range (℃) |
-40~60℃, >45℃ derating |
|||||||||||
Cooling |
Smart cooling |
|||||||||||
Noise (dB) |
<45 dB |
|||||||||||
Communication with BMS |
RS485; CAN |
|||||||||||
Weight (kg) |
30.5 |
|||||||||||
Size (mm) |
408W×638H×237D |
|||||||||||
Protection Degree |
IP65 |
|||||||||||
Installation Style |
Wall-mounted |
|||||||||||
Warranty |
5 years |
Copyright © Jiangsu Solarman Technology Co.,Ltd. All Rights Reserved - Privacy Policy